Exciter Model: DC2C

 

Model Equations and/or Block Diagrams

Parameters:

OEL OEL input: if = 2, LV gate; if < 2, subtract from error signal
UEL UEL input: if = 2, HV gate; if < 2, add to error signal
SCL SCL input: if = 2, LV gate; if < 2, subtract from error signal
Tr Regulator input filter time constant, s
Ka Regulator ouput gain, pu
Ta Regulator time constant, s
Tb Regulator denominator lag time constant, s
Tc Regulator numerator lead time constant, s
Vrmax Maximum controller output, pu
Vrmin Minimum controller output, pu
Ke Exciter field proportional constant, pu
Te Exciter field time constant, s
Kf Rate Feedback gain, pu
Tf1 Rate feedback time constant, s
E1 Exciter outout voltage for saturation factor SeE1, pu
SE1 Exciter saturation factor at exciter output voltage E1
E2 Exciter outout voltage for saturation factor SeE2, pu
SE2 Exciter saturation factor at exciter output voltage E2
Vemax Exciter output maximum limit
Vemin Exciter output minimum limit
Spdmlt If not zero, multiply output (Efd) by generator speed